Dynamometric 1Ph or 3 Ph Power & Power Factor Meter
Dynamometric instruments are used for measurement of active, reactive & absolute power in 1 Phase & 3 Phase systems for balanced / unbalanced load conditions. Watt, Var & VA instruments incorporate current coils, which are connected in series with the load & pressure coils of fine wire gauge, which are connected across the load. These instruments work on "Air cored Electro-Dynamometric" principle.
Power Factor meter incorporates two pressure coils one with non-inductive resistance in series & other with capacitance in series & are cross connected. The deflecting torque proportional to the phase angle between current & voltage vectors. The pointer rests anywhere on the scale when meter is not connected in the circuit, as there is no controlling torque.
Features
Scale
|
Linear. Side zero or center zero are available.
|
Housing
|
Sheet Metal (Black painted).
|
Terminal Protection
|
Shrouded terminals to protect from accident. (on request).
|
Electrical Specifications
Type
|
Dynamometric.
|
Operating Voltage
|
75V to 500V for 1Ph. 110V / 440V - PT secondary for 3Ph.
|
Burden
|
<1.25VA up to 75V, <2.5VA 100V to 150V, <5VA 200V to 300V<10VA 350V to 600V
|
Operating Current
|
0.5A to 10A for 1Ph. 1A / 5A - CT secondary for 3Ph.
|
Burden
|
<5VA up to 5A, <10VA up to 10A.
|
Frequency
|
45 ~ 65Hz. (400Hz. on request).
|
Accuracy
|
Class 1.5 for Watt / Var / Va. 2o for PF.
|
Insulation Resistance
|
Greater than 20M Îé at 500V.DC
|
Dielectric Test
|
2kV RMS for 1 minute.
|
Overload Continuous
|
1.2 times
|
Overload Short Time
|
2 time VN/10 times IN for 5 seconds.
|
Operating Temp.
|
-10oC to 55oC
|
Storage Temp.
|
-20oC to 70oC
|
Humidity
|
Up to 95% RH
|
Conforms To
|
I.S. 1248 / I.E.C. 60051 (Part 3) for WATT / VAR, (Part 5) for PF.
|
Mechanical Specifications
Size (mm)
|
Depth (mm)
|
Panel Cutout (mm)
|
Scale Length (mm)
|
Weight (gms.)
|
96 x 96 1Ph or 3Ph
|
See Table 1
|
92 x 92 +0.8
|
80 (approx.)
|
See Table 2
|
144 x 144 1Ph or 3Ph
|
138 x 138 +1.0
|
140 (approx.)
|
Table No. 1 (For Depth : in mm)
Para-meter
|
Watt Meter
|
Var Meter
|
VA Meter
|
PF Meter
|
1PH
|
3P1E
|
3P2E
|
3P3E
|
1PH
|
3P1E
|
3P2E
|
3P3E
|
1PH
|
3P1E
|
3P2E
|
3P3E
|
1PH
|
3P1E
|
3P2E
|
3P3E
|
96 x 96
|
80
|
80
|
100
|
100
|
-
|
-
|
100
|
-
|
80
|
-
|
100
|
-
|
80
|
80
|
-
|
-
|
144 x 144
|
85
|
85
|
125
|
165
|
-
|
-
|
125
|
165
|
85
|
-
|
125
|
165
|
125
|
125
|
-
|
-
|
Table No. 2 (For Weight : in approx. kg)
Para-meter
|
Watt Meter
|
Var Meter
|
VA Meter
|
PF Meter
|
1PH
|
3P1E
|
3P2E
|
3P3E
|
1PH
|
3P1E
|
3P2E
|
3P3E
|
1PH
|
3P1E
|
3P2E
|
3P3E
|
1PH
|
3P1E
|
3P2E
|
3P3E
|
96 x 96
|
0.5
|
0.5
|
0.7
|
0.7
|
-
|
-
|
0.7
|
-
|
0.5
|
-
|
0.8
|
-
|
0.6
|
0.7
|
-
|
-
|
144 x 144
|
1.0
|
1.0
|
1.4
|
1.7
|
-
|
-
|
1.4
|
1.8
|
1.8
|
-
|
1.5
|
1.8
|
1.2
|
1.4
|
-
|
-
|
Note : The connection diagram label is affixed on each meter.
Ordering information
- Type
- Size, Parameter, Phase & Element and Range
- Operating Voltage & PTR
- Operating Current & CTR
|